RMS Voltage Calculator
Enter a peak, peak-to-peak, RMS or average voltage for a sine, square, triangle, sawtooth, pulse or rectified wave, and this RMS voltage calculator returns the other three values with the crest factor and form factor. A 120 V US outlet, for example, peaks at 169.7 V and spans 339.4 V peak-to-peak.
How to Calculate RMS Voltage from Peak or Peak-to-Peak
For a sine wave, the RMS voltage is the peak voltage divided by √2, or 0.7071 times the peak. A 120 V, 60 Hz US outlet is rated in RMS, so it swings to 169.7 V at each crest and spans 339.4 V peak-to-peak. This RMS voltage calculator runs that conversion in any direction for seven waveforms.
- Choose the waveform. Square means a wave that swings equally above and below zero. A 0 to 5 V logic signal is a pulse train, so pick Pulse and set its duty cycle.
- Pick the value you know. Meters and nameplates give RMS; an oscilloscope shows peak or peak-to-peak. Average means the rectified average, the mean with the negative half flipped up.
- Enter the voltage and choose what to solve for. Pick the same quantity in both boxes and they swap. The other amplitudes, both factors and the formula follow the answer, and How this was worked out shows each step.
RMS Voltage Formula for Sine and Other Waves
RMS means root mean square: square the voltage at every instant, average the squares over a full cycle, then take the square root. The result is the DC voltage that heats a resistor equally, so a 120 V heater draws the same watts on 120 V AC as on 120 V DC. Power formulas, like the one in the amps to watts calculator, work in RMS values, and the Ohm's law calculator needs the RMS voltage of an AC load, never the peak.
- Vrms = root-mean-square voltage, in volts
- Vp = peak voltage, from zero to the crest, in volts
- √2 ≈ 1.4142, the crest factor of a sine wave
Example: a scope reads 170 V peak on a US receptacle, so Vrms = 170 ÷ 1.4142 = 120.2 V.
- Vpp = peak-to-peak voltage, lowest point to highest (this form holds for waves centered on zero)
- Vp = peak voltage, in volts
Example: 240 V split-phase peaks at 339.4 V, so Vpp = 678.8 V.
- Vavg = rectified average, the mean of the absolute value over a cycle
- Vp = peak voltage; π ≈ 3.1416
Example: 169.7 V peak gives Vavg = 108.0 V. Averaged without rectifying, a sine comes to 0 V.
RMS, Peak and Average Voltage Factors by Waveform
The 0.7071 factor belongs to the sine wave and its full-wave rectified form alone. Each ratio below is relative to the peak Vp, measured from zero.
| Waveform | Vrms ÷ Vp | Vavg ÷ Vp | Vpp ÷ Vp | Crest factor | Form factor |
|---|---|---|---|---|---|
| Sine | 0.7071 | 0.6366 | 2 | 1.4142 | 1.1107 |
| Square (symmetric) | 1 | 1 | 2 | 1 | 1 |
| Triangle | 0.5774 | 0.5 | 2 | 1.7321 | 1.1547 |
| Sawtooth | 0.5774 | 0.5 | 2 | 1.7321 | 1.1547 |
| Pulse, duty cycle D | √D | D | 1 | 1 / √D | 1 / √D |
| Half-wave rectified sine | 0.5 | 0.3183 | 1 | 2 | 1.5708 |
| Full-wave rectified sine | 0.7071 | 0.6366 | 1 | 1.4142 | 1.1107 |
Exact forms: 0.6366 is 2/π, 0.3183 is 1/π, 1.1107 is π/(2√2) and 1.5708 is π/2. Outlet and nameplate voltages are already RMS, so they go straight into the volts to amps calculator.
True RMS vs Average-Responding Meters
A meter that is not true-RMS measures the rectified average and multiplies it by 1.1107, the sine form factor. It reads a sine correctly and nothing else: a symmetric square wave shows 11.1% high, a triangle or sawtooth 3.8% low. The calculator lists that reading for those shapes; for a shape not listed here, measure it with a true-RMS meter.
Pulse and rectified waves sit on a DC level, and a true-RMS meter on its AC range reports only their AC part: use AC+DC mode, or combine the readings as √(Vdc² + Vac²). A pulse at 1% duty also has a crest factor of 10, so check the meter's crest-factor rating.
Where the RMS Voltage Calculator's Factors Come From
IEC 60050-103, the International Electrotechnical Vocabulary, defines RMS value as the positive square root of the mean square over a time interval (IEV 103-02-03), rectified value as the mean absolute value over a period (IEV 103-06-10), form factor as RMS over rectified value (IEV 103-06-14) and peak factor, usually called crest factor, as the maximum absolute value over RMS (IEV 103-06-15). A sine's mean square over one cycle is Vp²/2, giving Vp/√2; a triangle's straight ramps give Vp²/3 and Vp/√3.
IEC states both factors for alternating waves with a zero mean. For pulse and rectified waves the calculator uses the rectifier convention, taking their average as the DC level. The same ratios hold for current.
Common RMS and Peak Voltage Mistakes
- Using 0.7071 on a triangle wave. A 5 V peak triangle is 2.89 V RMS, not 3.54 V.
- Dividing peak-to-peak by √2. A 340 V peak-to-peak trace on a US outlet is 120.2 V RMS (340 / 2.8284), not 240 V.
- Rating parts to the RMS value. A filter capacitor behind a rectifier on a 120 V line charges toward the 170 V peak, so a 150 V part there is overstressed.
- Clipping a grounded scope's ground lead to a hot conductor. That is a line-to-ground fault through the probe; use a differential probe.
Disclaimer: These figures assume ideal waveforms; real mains is often slightly flat-topped by harmonics, so its peak can sit a few percent below RMS × 1.4142. Use test equipment rated for the circuit and consult a licensed electrician or professional engineer (PE) before relying on a figure for insulation or component ratings.
Frequently Asked Questions
What is RMS voltage?
RMS voltage is the steady DC voltage that would deliver the same heating power to a resistor as the AC waveform does. RMS stands for root mean square: square the instantaneous voltage, average the squares over a full cycle, then take the square root. For a sine wave it equals the peak divided by √2, so a 120 V US outlet, which is rated in RMS, peaks at 169.7 V. Meters, nameplates and utility voltages are RMS unless they say otherwise.
What is the difference between RMS and peak voltage?
Peak voltage is the highest instantaneous value a wave reaches, measured from zero, while RMS voltage is its heating-equivalent value. For a sine wave the peak is √2, or 1.4142, times the RMS: 120 V RMS peaks at 169.7 V and 230 V RMS at 325.3 V. That ratio is the crest factor, and it changes with the shape. A symmetric square wave has a crest factor of 1, so its peak and RMS match, while a triangle wave peaks at 1.7321 times its RMS.
How do you calculate the peak voltage of a wave?
Multiply the RMS voltage by the wave's crest factor: 1.4142 for a sine, 1 for a symmetric square and 1.7321 for a triangle or sawtooth. A 12 V AC transformer secondary peaks at 12 × 1.4142 = 16.97 V. From a peak-to-peak reading, halve it for any wave centered on zero, so 10 V peak-to-peak is 5 V peak. From the rectified average of a sine, multiply by π/2. To go from RMS straight to peak-to-peak on a sine, multiply by 2.8284.
What is the RMS voltage of a square wave?
A symmetric square wave's RMS voltage equals its peak, because the voltage squared is the same at every instant: a wave switching between +5 V and −5 V is 5 V RMS. A 0 to 5 V logic signal is different. It is a pulse train at 50% duty, so its RMS is 5 × √0.5 = 3.54 V and its average is 2.5 V. A meter that is not true-RMS reads a symmetric square wave about 11% high.
Get early access to OhmNexus Pro
Join the list for new calculators, guides and services, plus first access to our upcoming advanced and AI-assisted design tools. No spam; unsubscribe anytime.
Need more electrical tools?
View All Calculators