Current Divider Calculator

Enter the total current and two to six parallel branches, as resistance, conductance, inductance or capacitance, and this current divider calculator returns each branch current, its share of the total and, for resistors, the branch voltage and power. It can also solve the branch value for a target current, such as a meter shunt, and add a worst-case tolerance range.

By Saad Tahir, Electrical Engineer Updated

Calculator

Split a Current Between Branches

Common current divider examples
Branch 1's value is solved to carry this.
Adjust for your parts (optional)
Adds each branch's worst-case current range.
Flags any branch that needs more. Clear it to skip.
Rating needed = power × factor; 1 adds no margin.

Current Divider Result

—

Enter your values to split the current

How this was worked out

How to Use the Current Divider Calculator

A current divider is any set of parallel branches that shares one incoming current, each branch taking a share in inverse proportion to its resistance, so the lowest resistance carries the most. This current divider calculator applies the rule to two to six branches.

  1. Choose the known quantity: the total current, the branch voltage, or the total plus a target current for branch 1 to size a part such as a meter shunt.
  2. Set Enter branches as to resistance, conductance (siemens, the reciprocal of ohms), inductance or capacitance; inductors and capacitors start from the total current.
  3. Set the number of branches, fill each in with its own unit prefix, and pick the headline branch under Find the current in.
  4. Optional: Adjust for your parts adds a tolerance band, a resistor power rating (0.25 W pre-filled, a common through-hole size) and a safety factor for the power caution.

Current Divider Formula: The Current Division Rule

For two branches, the current in one branch is the total times the other branch's resistance over the sum of both.

Two-branch current divider ruleI1 = IT × R2 ÷ (R1 + R2)
  • I1 = current through branch 1, in amperes (A)
  • IT = total current into the pair (A)
  • R1, R2 = branch resistances (Ω)

Example: a 12 V car battery feeding a 6 Ω and a 4 Ω load in parallel supplies 5 A, so I1 = 5 × 4 ÷ 10 = 2 A flows through the 6 Ω load, leaving 3 A for the 4 Ω one.

For three or more branches, work in conductance (G = 1 / R); each branch takes its fraction of the total.

Current division for any number of branchesIk = IT × Gk ÷ GT
  • Ik = current through branch k (A)
  • IT = total current into the network (A)
  • Gk = branch conductance, 1 / Rk, in siemens (S)
  • GT = total conductance, the sum of every G (S)

Example: 2 A into 10 Ω, 20 Ω and 40 Ω: GT = 0.175 S, so the 10 Ω branch carries 2 × 0.1 ÷ 0.175 = 1.14 A, leaving 0.571 A and 0.286 A.

The smaller resistor carries more because every branch sees the same voltage, so by Ohm's law (I = V / R) half the resistance passes twice the current, and no branch carries more than the total. Inductors split by 1 / L the same way; capacitors split in proportion to capacitance (Ik = IT × Ck / CT), and frequency cancels from both. The Ohm's law calculator checks any one branch, and the volts to amps calculator handles a single load.

Run the rule backward to size a part: branch 1 needs the others' parallel resistance times the current they keep over the current it takes.

Resistance for a target branch currentR1 = Rp × (IT − I1) ÷ I1
  • R1 = resistance that branch 1 needs (Ω)
  • Rp = the other branches in parallel (Ω)
  • IT = total current (A)
  • I1 = current wanted through branch 1 (A)

Example: a 1 mA, 50 Ω meter reads 1 A full scale when a shunt takes the other 999 mA: R1 = 50 × 0.001 ÷ 0.999 = 50.05 mΩ.

Current Division for 2 Branches by Resistance Ratio

Only the ratio sets the split: 10 Ω and 20 Ω divide current like 10 kΩ and 20 kΩ.

R2 ÷ R1Branch 1 shareBranch 2 share10 A total splits as
150.0%50.0%5.00 A and 5.00 A
266.7%33.3%6.67 A and 3.33 A
375.0%25.0%7.50 A and 2.50 A
4.782.5%17.5%8.25 A and 1.75 A
990.0%10.0%9.00 A and 1.00 A
9999.0%1.0%9.90 A and 0.100 A

Current Division in Parallel Conductors: NEC 310.10(G)

Paralleled conductors are a current divider, which is why NEC 2023 (NFPA 70-2023) is strict about them. Apart from two narrow exceptions, NEC 310.10(G)(1) allows paralleling only in 1/0 AWG and larger, and NEC 310.10(G)(2) requires the same length, material, circular-mil size, insulation type and termination so the current splits evenly.

Take a 400 A feeder built from two sets of 3/0 copper, 100 ft and 110 ft long. At the 0.0766 Ω per 1,000 ft that NEC Chapter 9 Table 8 lists for uncoated stranded 3/0 copper, the runs measure 7.66 mΩ and 8.426 mΩ, so the shorter set carries 400 × 110 / 210 = 209.5 A, almost 5% over the 200 A that NEC 310.16 lists for 3/0 copper at 75°C. The wire resistance calculator gives each run's resistance, and IEC 60364-5-52 covers paralleled cables too.

Units follow NIST SP 330: the siemens, 1 S = 1 A/V, is the SI unit of conductance.

Common Current Divider Mistakes

  • Putting the branch's own resistance on top. I1 takes R2 in the numerator; swapped, each branch gets the other one's current.
  • Using it on a series string. Series parts share one current; the voltage divides instead.
  • Mixing prefixes. A 4.7 left in Ω beside a 1 kΩ branch is a 1,000 to 1 error.
  • Trusting nominal values. With 5% resistors, the 4.00 A branch of 6 A into 100 Ω and 200 Ω ranges from 3.86 A to 4.13 A.
  • Mixing part types. A capacitor beside a resistor or a motor splits AC current by impedance and phase angle, which this calculator does not model.

Disclaimer: Results assume ideal parts at the values entered (resistors, or all-inductor or all-capacitor branches at AC); real parts drift with tolerance and temperature. Paralleling building conductors falls under the NEC as adopted by your authority having jurisdiction (AHJ), so have a licensed electrician or PE confirm installation decisions.

Frequently Asked Questions

What is a current divider?

A current divider is a group of parallel branches that shares one incoming current, each branch taking a share inversely proportional to its resistance. Two equal resistors split the current in half, while 1 kΩ beside 4.7 kΩ sends 82.5% of it through the 1 kΩ part. You meet one in ammeter shunts, which route most of a large current around a delicate meter, and in paralleled feeder conductors, where a longer run quietly hands extra current to the shorter one.

What is the current divider formula?

For two branches the current divider formula is I1 = Itotal × R2 / (R1 + R2): the current in branch 1 equals the total current times the other branch's resistance, divided by the sum of both. For any number of branches, Ik = Itotal × Gk / GT, where G = 1 / R is each branch's conductance and GT is the sum of all of them. With 6 A into 100 Ω and 200 Ω, I1 = 6 × 200 / 300 = 4 A, and the 200 Ω branch takes the remaining 2 A.

How do you calculate current in a parallel circuit?

Find the voltage across the branches, then divide it by each branch's resistance. Every branch in parallel sees the same voltage, so a 12 V battery feeding a 6 Ω load and a 4 Ω load drives 12 / 6 = 2 A through the first and 12 / 4 = 3 A through the second, 5 A in all. When you know the total current but not the voltage, use the current divider rule instead, Ik = Itotal × Gk / GT. This calculator starts from either one, for up to six branches.

How to calculate total current in a parallel circuit?

Add up the branch currents. Kirchhoff's current law says the current flowing into a junction equals the current flowing out, so the total current is the sum of every branch: branches carrying 1.5 A, 0.75 A and 0.25 A draw 2.5 A from the supply. If you only know the voltage and the resistances, work out each branch current as V / R first, then add them. Set the known quantity to branch voltage and this calculator does that sum for you; from a known total it runs the check the other way.

Need more electrical tools?

View All Calculators