Wire Resistance Calculator
Find the DC resistance of any wire from its material, gauge or cross-section, length and temperature. Enter 12 AWG and 100 ft, or 2.5 mm² and 50 m, and get ohms, ohms per 1000 ft and ohms per km, computed from IACS resistivity or read from NEC Chapter 9 Table 8.
How to Calculate the Resistance of a Wire
- Pick the material. Copper is selected to start; aluminum, silver, gold, nickel and tungsten carry their own resistivity and coefficient.
- Enter the size as an AWG or kcmil gauge, a cross-section in mm², or a diameter in mm or inches.
- Enter the length in feet or meters. The result is for one conductor unless you set the conductor path to an out-and-back pair.
- Check the temperature. It starts at 68 °F (20 °C), the resistivity reference; enter 167 °F (75 °C) to match NEC tables.
- Open Adjust for your install to switch to the NEC Chapter 9 Table 8 basis, add a current for the I × R drop and I²R loss, or change Solve for to find the length or equivalent gauge for a target resistance.
Wire resistance formula: R = ρL/A, then the temperature correction
100 feet of 12 AWG copper has a resistance of 0.1588 Ω at 68 °F. Resistance equals resistivity times length divided by cross-sectional area. Resistivity (ρ) is a material property, 1.7241 × 10-8 Ω·m for annealed copper wire at 20 °C. Double the length and the resistance doubles; double the area and it halves.
- R = resistance of one conductor (ohms, Ω)
- ρ = resistivity of the material at 20 °C (Ω·m)
- L = conductor length (m)
- A = cross-sectional area (m²)
Example: 12 AWG is 3.309 mm², or 3.309 × 10-6 m², and 100 ft is 30.48 m, so R = (1.7241 × 10-8 × 30.48) ÷ (3.309 × 10-6) = 0.1588 Ω.
Warm wire has more resistance. Copper gains 0.393% per °C, so the same 100 ft reads 0.1932 Ω at 167 °F (75 °C), about 21.6% more. The coefficient (α) is 0.00393 for copper and 0.00403 for aluminum, both referenced to 20 °C.
- RT = resistance at the operating temperature (Ω)
- R20 = resistance at 20 °C (Ω)
- α = temperature coefficient of resistance at 20 °C (per °C)
- T = conductor temperature (°C)
Example: 0.1588 × [1 + 0.00393 × (75 − 20)] = 0.1588 × 1.216 = 0.1932 Ω.
Once you have R, Ohm's law gives the rest. At 15 A that single 100 ft conductor drops 15 × 0.1588 = 2.382 V and turns 15² × 0.1588 = 35.73 W into heat. The amps to volts calculator runs that V = I × R step for any current.
Copper and aluminum wire resistance per 1000 ft and per km
The table below is what this calculator returns for one conductor at 68 °F (20 °C). Conductor-grade aluminum is 61% IACS, so every aluminum value is 1/0.61 = 1.64 times the copper value in the same row; 10 AWG copper is 0.9988 Ω per 1000 ft and 10 AWG aluminum is 1.637 Ω. For diameters, areas and ampacity by gauge, see the wire gauge chart.
| Size | Copper (Ω/1000 ft) | Copper (Ω/km) | Aluminum (Ω/1000 ft) | Aluminum (Ω/km) |
|---|---|---|---|---|
| 14 AWG | 2.525 | 8.285 | 4.14 | 13.58 |
| 12 AWG | 1.588 | 5.211 | 2.604 | 8.542 |
| 10 AWG | 0.9988 | 3.277 | 1.637 | 5.372 |
| 8 AWG | 0.6282 | 2.061 | 1.03 | 3.379 |
| 6 AWG | 0.3951 | 1.296 | 0.6476 | 2.125 |
| 4 AWG | 0.2485 | 0.8152 | 0.4073 | 1.336 |
| 3 AWG | 0.197 | 0.6464 | 0.323 | 1.06 |
| 2 AWG | 0.1563 | 0.5127 | 0.2562 | 0.8404 |
| 1 AWG | 0.1239 | 0.4066 | 0.2031 | 0.6665 |
| 1/0 AWG | 0.09827 | 0.3224 | 0.1611 | 0.5285 |
| 2/0 AWG | 0.07793 | 0.2557 | 0.1278 | 0.4192 |
| 3/0 AWG | 0.0618 | 0.2028 | 0.1013 | 0.3324 |
| 4/0 AWG | 0.04901 | 0.1608 | 0.08035 | 0.2636 |
Why NEC Chapter 9 Table 8 reads higher than the computed value
Switch the data basis and 100 ft of stranded 12 AWG copper at 75 °C reads 0.198 Ω instead of 0.1932 Ω. Both are right. NEC 2023 (NFPA 70-2023) Chapter 9, Table 8 lists DC resistance at 75 °C for solid and Class B stranded conductors, and a stranded conductor carries about 2% more metal length because each strand spirals around the core. Table 8 Note 4 fixes copper at 100% IACS and aluminum at 61% IACS, and Note 2 gives its own temperature equation with α = 0.00323 for copper and 0.00330 for aluminum referenced to 75 °C. Use the Table 8 basis when the number has to match a plan reviewer's table or the voltage-drop informational note under NEC 210.19 and 215.2(A)(2); use the computed basis for any other metal, metric size, or temperature far from 75 °C. To pick a conductor for a load, use the wire size calculator; this page only reports resistance.
Outside North America, IEC 60228 lists maximum resistance per km at 20 °C by class: 2.5 mm² class 2 copper is capped at 7.41 Ω/km, about 7% above the 6.896 Ω/km computed here, since the standard sets a ceiling.
Common wire resistance mistakes
- Using the textbook copper value. 1.68 × 10-8 Ω·m describes pure laboratory copper. Wire is specified at 1.7241 × 10-8 (100% IACS), 2.6% higher, the value every published wire table rests on.
- Correcting NEC values from 20 °C. Table 8 numbers are already at 75 °C. Treating 1.98 Ω per 1000 ft as a room-temperature figure and adding 21.6% again overstates 12 AWG by a fifth.
- Forgetting the return path. A circuit has two conductors, so the resistance the load sees is twice the single-conductor number.
- Applying DC resistance to large AC conductors. At 60 Hz, skin effect adds under 1% through 4/0 copper but grows with size; for 500 kcmil and up, read the AC resistance in NEC Chapter 9 Table 9.
Disclaimer: This wire resistance calculator computes DC resistance from published resistivity and gauge geometry, or from NEC Chapter 9 Table 8, for the values you enter. Real conductors vary with alloy, stranding, temper and temperature, and the result is neither a voltage-drop compliance check nor a conductor size. Verify code-related values against the edition your authority having jurisdiction (AHJ) enforces, and consult a licensed electrician or professional engineer for design decisions.
Frequently Asked Questions
What is the resistance of 12 gauge copper wire per foot?
12 AWG copper measures 1.588 milliohms per foot at 68 °F (20 °C), which is 1.588 Ω per 1000 ft or 5.211 Ω per km, computed from 100% IACS resistivity. NEC Chapter 9 Table 8 lists 1.98 Ω per 1000 ft for stranded 12 AWG, but that figure is at 75 °C and includes the extra length of the spiraled strands; corrected back to 20 °C with the table's own coefficient it becomes 1.63 Ω per 1000 ft, within 2.5% of the computed value. So 100 ft of 12 AWG is about 0.16 Ω cold and 0.19 to 0.20 Ω at operating temperature.
How do you calculate the resistance of a wire?
Multiply the material's resistivity by the length and divide by the cross-sectional area: R = ρL/A, with ρ in Ω·m, L in meters and A in square meters. For 50 m of 2.5 mm² copper, R = (1.7241 × 10-8 × 50) / (2.5 × 10-6) = 0.3448 Ω. If the wire runs warmer than 20 °C, multiply by 1 + α(T − 20), where α is 0.00393 per °C for copper. In US units the same math is R = K × L / cmil, with K = 10.371 Ω·cmil/ft for copper at 20 °C and the length in feet.
Why is aluminum wire resistance higher than copper?
Conductor-grade aluminum conducts 61% as well as copper on the IACS scale, so a conductor of the same size has 1/0.61 = 1.64 times the resistance: 10 AWG aluminum is 1.637 Ω per 1000 ft against 0.9988 Ω for copper at 20 °C. Aluminum is still used because it weighs about 30% as much as copper for the same volume and costs less, which is why 2/0 aluminum is the rough electrical equal of 1 AWG copper at about half the weight. Its temperature coefficient is also slightly higher, 0.00403 against 0.00393 per °C, so the gap widens a little as the wire heats.
Does wire resistance increase with temperature?
Yes, for every metal conductor. Copper rises 0.393% per °C, so a wire at 75 °C (167 °F) has 21.6% more resistance than at 20 °C, and at 90 °C it has 27.5% more. The relationship is close to linear for copper and aluminum across the range building wire sees, which is why the NEC gives a one-line equation in Chapter 9 Table 8 Note 2. Cold works the other way: at 0 °F (minus 18 °C) copper has about 15% less resistance than at room temperature. Resistor alloys such as constantan are blended so the coefficient is nearly zero.
Get early access to OhmNexus Pro
Join the list for new calculators, guides and services, plus first access to our upcoming advanced and AI-assisted design tools. No spam; unsubscribe anytime.
Need more electrical tools?
View All Calculators