Wire Gauge Chart

Look up any American Wire Gauge from 4/0 to 40 and read its exact diameter, cross-sectional area in mm² and kcmil, resistance, and NEC ampacity for copper and aluminum. You can also work backward, entering a millimeter or kcmil size to find the nearest standard AWG. Every value comes from the AWG geometric standard and NEC Table 310.16.

By Saad Tahir, Electrical Engineer Updated

Calculator

Wire Gauge Lookup

Gauge Properties

Pick a gauge to see its properties

Wire Gauge Chart (AWG Sizes)

A wire gauge chart maps each American Wire Gauge (AWG) number to a fixed diameter, cross-sectional area, and resistance. The scale runs backward, so a bigger number means a thinner wire. 12 AWG measures 0.0808 inches (2.053 mm) across; 4/0, which is nine sizes larger, reaches 0.460 inches (11.68 mm). Find your gauge in the first column and read across, or match a known area in mm² or kcmil to the closest row.

Wire gauge thickness comparison: 4/0, 1/0, 4, 8, 10, 12, and 14 AWG copper conductors drawn to scale, showing a higher AWG number is a thinner wire
Drawn to scale, the conductor gets thinner as the AWG number rises. 4/0 has about seven times the diameter of 14 AWG.

The full chart runs from the largest building conductor down to fine signal wire. Resistance is for copper at 20°C; aluminum of the same gauge has about 1.64 times that value.

AWGDiameter (in)Diameter (mm)Area (mm²)Area (kcmil)Resistance, Cu (Ω/1000 ft)
4/00.4611.681072120.049
3/00.409610.4851680.0618
2/00.36489.26667.41330.0779
1/00.32498.25153.51060.0983
10.28937.34842.483.70.124
20.25766.54433.666.40.156
30.22945.82726.752.60.197
40.20435.18921.241.70.248
50.18194.62116.833.10.313
60.1624.11513.326.30.395
70.14433.66510.520.80.498
80.12853.2648.3716.50.628
90.11442.9066.6313.10.792
100.10192.5885.2610.40.999
110.090742.3054.178.231.26
120.080812.0533.316.531.59
130.071961.8282.625.182.0
140.064081.6282.084.112.53
150.057071.451.653.263.18
160.050821.2911.312.584.02
170.045261.151.042.055.06
180.04031.0240.8231.626.38
190.035890.91160.6531.298.05
200.031960.81180.5181.0210.2
220.025350.64380.3260.64216.1
240.02010.51060.2050.40425.7
260.015940.40490.1290.25440.8
280.012640.32110.0810.1664.9
300.010030.25460.05090.101103
320.007950.20190.0320.0632164
340.0063050.16010.02010.0398261
360.0050.1270.01270.025415
380.0039650.10070.007970.0157660
400.0031450.079870.005010.009891050

AWG ampacity chart: how many amps each wire carries

Ampacity is the current a wire carries continuously without overheating. At a 75°C termination under NEC Table 310.16, 14 AWG copper carries 20 A, 12 AWG carries 25 A, and 10 AWG carries 35 A. Aluminum of the same size carries less, because it conducts about 61% as well as copper.

The column you read depends on the terminals as much as the wire. Most breakers and lugs are rated 75°C, but nonmetallic (NM-B) cable is held to the 60°C column by NEC 334.80, which is why 12 AWG Romex is protected at 20 A rather than 25 A.

Copper and aluminum ampacity at 60, 75, and 90°C, with the largest breaker or fuse each conductor allows:

AWGCopper (A)Aluminum (A)Max OCPD, Cu (A)
60°C75°C90°C60°C75°C90°C
14152025Not rated15
1220253015202520
1030354025303530
840505535404550
655657540505570
470859555657590
385100115657585100
2951151307590100125
111013014585100115150
1/0125150170100120135150
2/0145175195115135150175
3/0165200225130155175200
4/0195230260150180205250

The last column is the largest device the conductor itself allows, rounded up to the next standard rating under NEC 240.4(B) where the ampacity does not match a standard size and the result stays at or below 800 A. The values shown are for copper; aluminum has its own small-conductor caps of 15 A for 12 AWG and 25 A for 10 AWG. For 14, 12, and 10 AWG copper the small-conductor rule holds it to 15, 20, and 30 A (NEC 240.4(D)). Your real breaker also depends on the load and whether it runs for three hours or more, which the wire size calculator works out from the current.

Every figure here assumes no more than three current-carrying conductors in a raceway and a 30°C (86°F) ambient. Bundle more wires together or run them somewhere hot, and the usable ampacity drops by the correction factors in NEC 310.15.

How American Wire Gauge works

AWG is defined by a formula, not a stored list. Each size comes from a geometric ratio anchored to two reference points, 36 AWG and 4/0, with 39 equal steps between them. The diameter of one gauge is always about 1.123 times the next thinner size.

AWG diameter d = 0.005 × 92(36 − n) ÷ 39
  • d = conductor diameter in inches
  • n = gauge number; the 1/0 to 4/0 sizes continue below 1 as n = 0, −1, −2, −3

Example: 12 AWG gives 0.005 × 9224 ÷ 39 = 0.0808 in (2.053 mm).

Two shortcuts fall out of that ratio and save a lookup in the field. Drop the gauge number by 6 and the diameter roughly doubles; drop it by 3 and the area roughly doubles. Ten steps change the area about tenfold, so 10 AWG holds close to ten times the copper of 20 AWG.

AWG to mm² and kcmil conversion

To convert a gauge to metric, square its diameter in mils to get circular mils, then scale. 12 AWG is 80.8 mils across, which is 6,530 circular mils, or 6.53 kcmil, or 3.31 mm². The quick factor is 1 kcmil = 0.5067 mm².

Area in mm² A = cmil × 0.0005067
  • A = cross-sectional area in square millimeters (mm²)
  • cmil = area in circular mils, the diameter in mils squared

Example: 12 AWG is 80.8 mils across, so 80.8² = 6,530 cmil = 3.31 mm².

Cable sold in metric sizes follows IEC 60228, which sets its own rounded mm² steps. This table pairs each AWG with the nearest standard metric conductor, so you can cross a US wire size to a European one.

AWGDiameter (mm)Area (mm²)Area (kcmil)Nearest metric cable (mm²)
4/011.6810721295
2/09.26667.413370
1/08.25153.510650
17.34842.483.735
26.54433.666.435
45.18921.241.725
64.11513.326.316
83.2648.3716.510
102.5885.2610.46
122.0533.316.534
141.6282.084.112.5
161.2911.312.581.5
181.0240.8231.620.75
200.81180.5181.020.5
220.64380.3260.6420.5
240.51060.2050.4040.5

The old British Standard Wire Gauge (SWG) numbers wire the same way but with different diameters, so 12 SWG and 12 AWG are not the same conductor. Match by area or diameter, never by the number alone. If you only know the load, the watts to amps calculator gives the current, which is the real starting point for choosing a size.

Copper versus aluminum, solid versus stranded

Copper and aluminum of the same AWG share the same diameter, but aluminum carries less current and has about 1.64 times the resistance. A 100 A feeder that takes 3 AWG copper needs 1 AWG aluminum, one full size larger. Aluminum also wants terminals marked CO/ALR or AL-CU and an antioxidant joint compound.

Solid and stranded wire of the same gauge have the same copper area and nearly the same resistance. Stranded bends more easily and its overall diameter runs a little larger, thanks to the gaps between strands, though the AWG still refers to the combined copper cross-section rather than the outer bundle. A code like 7/30 reads as seven strands of 30 AWG twisted together; their total copper area sets the wire’s overall gauge.

Common wire gauge mistakes

A handful of errors show up again and again when people read a gauge chart.

  • Reading the scale backward. A higher number is a thinner wire. 14 AWG is smaller than 10 AWG.
  • Sizing a breaker from the 90°C column. The 90°C ampacity is only for the derating math; terminations cap you at the 60 or 75°C column (NEC 110.14(C)).
  • Treating aluminum like copper. Aluminum needs about one size larger for the same current, plus rated terminals.
  • Swapping AWG and SWG. The same number is a different diameter in each system.
  • Ignoring heat and bundling. The chart’s amps assume three conductors at 30°C; a hot attic or a packed conduit lowers them.

These charts follow the 2023 National Electrical Code (NFPA 70-2023). Adopted editions and local amendments vary by area, and your authority having jurisdiction has the final say, so treat this as a reference, not a replacement for the code book or a licensed electrician.

Frequently Asked Questions

How many amps can 12-gauge wire handle?
12-gauge copper wire handles 20 amps on a standard 60°C or Romex circuit, and up to 25 amps at a 75°C termination (NEC 310.16). Household 12 AWG branch circuits are protected at 20 amps under the small-conductor rule in NEC 240.4(D). 12-gauge aluminum carries less and is limited to 15 amps.
How many amps can 10-gauge wire handle?
10-gauge copper carries 30 amps at 60°C and 35 amps at 75°C, and NEC 240.4(D) caps its breaker at 30 amps. That makes 10 AWG the standard choice for a 30-amp circuit such as an electric dryer or a small water heater. 10-gauge aluminum is limited to about 25 amps.
How many amps can 14-gauge wire handle?
14-gauge copper carries 15 amps and must be protected at 15 amps under NEC 240.4(D), even though its 75°C ampacity is 20 amps. It is the standard wire for 15-amp lighting and receptacle circuits, and it should never sit on a 20-amp breaker.
Is a higher-gauge wire thicker or thinner?
A higher AWG number means a thinner wire. The gauge roughly counts how many times the wire was drawn through a die, so 20 AWG is much thinner than 10 AWG. Below 1 AWG the sizes continue as 1/0, 2/0, 3/0, and 4/0, which get progressively thicker.
What is 12 AWG in mm2?
12 AWG equals 3.31 mm² of cross-sectional area, or 6.53 kcmil. The nearest standard metric cable size is 4 mm² under IEC 60228. To convert any gauge, square its diameter in mils to get circular mils, then multiply by 0.0005067.
What does AWG stand for?
AWG stands for American Wire Gauge, the standard wire-sizing system in North America. It sets each size by a fixed geometric ratio, so one gauge is always about 1.123 times the diameter of the next thinner size. The system is also called the Brown and Sharpe (B&S) gauge.

Need more electrical tools?

View All Calculators