Voltage Drop Calculator

This voltage drop calculator shows the volts and percent lost on a wire run, the voltage left at the load and how the run compares with the 3% NEC note. It reads NEC Chapter 9 Tables 8 and 9 for AWG runs or IEC 60228 resistance for mm² cable, on DC, single-phase or three-phase circuits. It can also work backward to the longest one-way run that stays within your drop limit.

By Saad Tahir, Electrical Engineer Updated

Calculator

Voltage Drop on a Run

Common runs
Source to load, not the round trip.
Line-to-line for three-phase.
NEC informational notes: 3% per branch circuit, 5% feeder plus branch.
Adjust for your install (optional)
Motors and mixed loads run 0.8 to 0.9; resistive loads are 1.0. On large feeders a lower PF raises the drop.
NEC tables are at 167 °F (75 °C). A lightly loaded conductor runs cooler and drops less.

Voltage Drop

—

Enter the run to see the drop

How this was worked out

How to Calculate Voltage Drop on a Wire Run

To calculate voltage drop, multiply 2 by the load current, the conductor resistance per 1,000 feet and the one-way length, then divide by 1,000 (on three-phase, √3 replaces the 2). A 20 A load on 12 AWG copper 50 feet from a 120 V panel drops about 4 V (3.3%), just past the NEC’s 3% branch-circuit note. To run the voltage drop calculation:

  1. Pick the standard. NEC / CEC reads AWG, feet and Chapter 9 of NEC 2023 (NFPA 70-2023); IEC 60364 / BS 7671 reads mm², meters and IEC 60228.
  2. Choose what to solve for: the drop, the longest run for your limit, or the smallest size that meets it (finish sizing in the wire size calculator).
  3. Enter the run: supply, material, size, load current, one-way length and voltage. Starting from watts? Use the watts to amps calculator.
  4. Adjust for power factor or steel conduit (NEC AC), conductor temperature, or parallel sets.

Voltage Drop Formula: K-Factor, NEC Table 8 and Table 9

The voltage drop formula is Vd = (2 × I × R × L) / 1000 for single-phase and DC, and Vd = (√3 × I × R × L) / 1000 for three-phase. The K-factor version, Vd = (2 × K × I × L) / CM, is the same math: CM is the conductor area in circular mils, and K (12.9 copper, 21.2 aluminum) is Table 8 resistance at 75°C times CM / 1000 (12 AWG: 1.98 × 6,530 / 1000).

Voltage drop, single-phase or DCVd = (2 × I × R × L) ÷ 1000
  • Vd = volts lost along the run
  • I = load current (amps)
  • R = NEC Chapter 9 Table 8 resistance (Ω per 1,000 ft at 75°C)
  • L = one-way length (feet); the 2 covers the return conductor

Example: 12 AWG copper (R = 1.98) at 20 A for 50 ft drops (2 × 20 × 1.98 × 50) ÷ 1000 = 3.96 V.

On large AC feeders skin effect raises R and reactance adds XL × sin θ as power factor falls, so NEC AC runs here use Table 9 effective impedance. At PF 1, 12 AWG reads 2.0 Ω there, so the run above shows 4.00 V.

Effective impedance (NEC Table 9)Ze = R × PF + XL × sin θ
  • Ze = effective impedance used in place of R (Ω per 1,000 ft)
  • R, XL = Table 9 resistance and reactance for the conduit material
  • PF = power factor
  • θ = load angle, arccos(PF); sin θ = 0 at PF 1

Example: 500 kcmil copper in steel at 0.85 PF: Ze = 0.029 × 0.85 + 0.048 × 0.527 = 0.0499, so 380 A over 300 ft at 480 V three-phase drops 9.86 V, where the K form, with √3 for the 2, gives only 5.09 V.

Voltage Drop Chart per 100 Feet: Copper at 75°C (NEC Table 9)

Full-load drop for 100 feet one-way, single-phase AC at PF 1 in PVC conduit. Max load is the NEC 240.4(D) limit for 14 to 10 AWG and the Table 310.16 75°C ampacity above.

Copper AWGDrop per amp (V)Max load (A)Drop at max load (V)
140.62159.30
120.40208.00
100.24307.20
80.156507.80
60.098656.37
1/00.0241503.60

Is 3% Voltage Drop an NEC Requirement?

For most circuits, no. The NEC 210.19 and 215.2(A)(2) Informational Notes suggest 3% on a branch circuit or feeder and 5% combined, and under NEC 90.5(C) such notes are not enforceable. Mandatory limits come only from specific articles: NEC 647.4(D) for Article 647 sensitive-electronics systems (1.5% branch, 2.5% total; 1% and 2.0% on receptacle circuits) and NEC 695.7(D) for fire pumps (5% running). Otherwise the equipment’s minimum voltage binds, through NEC 110.3(B). Canada’s CEC (CSA C22.1) sets its own rule; check with your inspection authority.

BS 7671 Appendix 4 uses 3% on lighting and 5% on other circuits, so 2.5 mm² at 16 A over 30 m (8.51 V, 3.7% of 230 V) clears only the second. The IEC mode reads IEC 60228 resistance only: on 35 mm² and larger, a load below unity power factor adds reactive drop the result leaves out.

Conductor Temperature Changes the Voltage Drop

NEC tables list resistance at 75°C (167°F), a conductor at full ampacity; a lightly loaded one runs cooler and drops less. Table 8 Note 2 corrects it: R2 = R1 × [1 + α (T2 − 75)], where α is 0.00323 for copper or 0.00330 for aluminum. A 15 A load 75 feet out on 12 AWG at 120 V drops 4.50 V (3.75%) at 75°C but 4.14 V (3.45%) at 50°C. Applying it to Table 9 AC resistance is an approximation; the wire resistance calculator gives resistance alone.

Three-Phase and DC Voltage Drop, Parallel Conductors

Three-phase uses √3 instead of 2 because, on a balanced load, the line-to-line drop is √3 times the drop in each conductor; enter line-to-line volts. DC voltage drop has no reactance, but low voltage magnifies it: 10 A on 12 AWG over 25 feet loses 0.99 V, 4.1% of 24 V. NEC 310.10(G) permits parallel sets only at 1/0 AWG and larger.

Common Voltage Drop Calculator Mistakes

  • Entering the round-trip length. The 2 already counts the return conductor.
  • Using 20°C resistivity, about 18% below the 75°C NEC tables.
  • Ignoring reactance on NEC copper runs above 1/0 AWG (from 2 AWG in steel conduit), where a resistance-only voltage loss formula reads low.
  • Stopping at the drop check. A short run can sit well under 3% on a conductor too small to carry the load.

Disclaimer: This voltage drop calculator applies NEC Chapter 9 and IEC 60228 data to your inputs. Adopted NEC editions and local amendments vary, so confirm the result with your authority having jurisdiction (AHJ) and have a licensed electrician or professional engineer check the design.

Frequently Asked Questions

What is voltage drop?

Voltage drop is the voltage lost along a conductor’s resistance and reactance between the source and the load, so the equipment receives less than the supply voltage. A 30 A load 80 feet from the panel on 10 AWG copper loses (2 × 30 × 1.2 × 80) / 1000 = 5.76 V, or 2.40% of 240 V, using the NEC Table 9 value of 1.2 Ω per 1,000 ft. Too much drop shows up at the load: a motor draws more current and runs hot, lighting dims, and an LED driver or EV charger can drop out.

How much voltage drop is acceptable?

Under the NEC, the accepted target is 3% on a branch circuit or a feeder and 5% for the two combined, from the NEC 210.19 Informational Note and NEC 215.2(A)(2) Informational Note No. 2. NEC 90.5(C) makes those notes explanatory rather than enforceable, so the code sets no general maximum. Mandatory limits exist only for specific equipment: NEC 647.4(D) for Article 647 sensitive-electronics systems (1.5% branch and 2.5% total, or 1% and 2.0% on receptacle circuits with the load taken at 50% of the branch rating) and 5% while running for fire pump motors (NEC 695.7(D)). Equipment nameplate minimums bind through NEC 110.3(B).

What is the voltage drop on 12 gauge wire?

About 0.4 V per amp for every 100 feet of one-way run on 12 AWG copper, single-phase: NEC Table 9 lists 2.0 Ω per 1,000 ft, and 2 × 2.0 × 100 / 1000 = 0.40 V. At 20 A and 120 V the drop reaches 3% at 45 feet one-way: 0.03 × 120 × 1000 / (2 × 20 × 2.0) = 45 ft. At 240 V the same 20 A load can run 90 feet. Past those distances most electricians step up to 10 AWG, which stretches the 120 V run to about 75 feet.

How do you calculate DC voltage drop?

Use the same formula with the DC resistance listed in NEC Chapter 9 Table 8: Vd = (2 × I × R × L) / 1000, where the 2 counts the positive and negative conductors. DC has no reactance or power factor, so nothing else enters the math. A 20 A load on 10 AWG copper 15 feet from a 12 V battery drops (2 × 20 × 1.24 × 15) / 1000 = 0.744 V, which is 6.2% of 12 V; the same run at 120 V would be 0.6%. To size the cable for a 12, 24 or 48 V system, use the DC wire size calculator.