DC Wire Size Calculator

Size wire for 12 V, 24 V and 48 V battery, inverter, RV, marine, automotive and solar DC circuits. Enter the voltage, load and one-way run and get the AWG and mm² that pass both the voltage-drop limit and the ampacity table, with the fuse that protects it.

By Saad Tahir, Electrical Engineer Updated

Calculator

DC Wire Sizing

Common DC circuits
Blank uses Isc for the drop, the conservative choice.
Adjust for your install (optional)

Recommended DC Wire

—

Enter the voltage, load and run length to size the wire

How this was worked out

How to Size DC Wire for 12 V, 24 V, 48 V and Solar Runs

A DC conductor must pass two checks; keep the larger answer: it must carry the current without overheating (ampacity), and it must hold the round-trip voltage drop inside your limit. At 12 V the drop check nearly always decides. A 10 A fridge on a 20 ft run needs 8 AWG copper to stay under 3 percent, even though 14 AWG carries 10 A.

  1. Pick the application. It sets the ampacity table and the drop limit: NEC Table 310.16 for battery, inverter and RV circuits, NEC 690.8 for solar, ABYC E-11 Table 6A for boats and vehicles.
  2. Set the system voltage: 12, 24 or 48 V, or a custom value. Solar mode asks for the string voltage (Vmp).
  3. Enter the load in amps or watts. Watts are converted with the voltage and, for battery and RV circuits, the inverter efficiency.
  4. Enter the one-way run length; the return conductor is added for you.
  5. Check the allowable drop: 3 percent for battery circuits, 2 percent for solar, 3 or 10 percent on boats and vehicles by circuit type.
  6. Read the gauge, mm², drop, ampacity basis, fuse or breaker, and governing limit.

What the Result Means: Voltage Drop and Ampacity

Battery, solar, RV and automotive modes take resistance from NEC Chapter 9 Table 8 at 75°C for stranded conductors, so warm wire in a battery box or engine bay is sized honestly.

Voltage drop on a DC runVd = (2 × I × L × R) ÷ 1000
  • Vd = voltage drop (V)
  • I = load current (A)
  • L = one-way length (ft)
  • R = Ω per 1000 ft, NEC Chapter 9 Table 8

Example: 10 A, 20 ft, 8 AWG copper (0.778 Ω/kft): (2 × 10 × 20 × 0.778) ÷ 1000 = 0.311 V, 2.6 percent of 12 V.

Marine mode uses the ABYC E-11 circular-mil formula instead, so results match the ABYC 3 and 10 percent tables. The two methods can differ by one size near the limit (bilge pump preset): 10 AWG at 2.6 percent under ABYC, 3.1 percent by Table 8.

ABYC E-11 conductor areaCM = (K × I × 2L) ÷ E
  • CM = circular mils (round up to the next AWG)
  • K = 10.75, copper constant
  • 2L = round-trip length (ft)
  • E = allowable drop (V)

Example: 15 A, 10 ft one way, 0.36 V allowed (3 percent of 12 V): (10.75 × 15 × 20) ÷ 0.36 = 8,958 cmil, so 10 AWG at 10,380 cmil.

12 V Wire Size Chart: Maximum One-Way Run at 3 Percent Drop

Engine-generated for copper at 12 V, a 3 percent drop and non-continuous loads. Read down to your gauge and across to your current for the longest one-way run; "not rated" means the gauge cannot carry that current under NEC 310.16 and the 240.4(D) caps. Double the lengths at 24 V, quadruple them at 48 V.

Copper gauge10 A20 A30 A
14 AWG5.7 ftnot ratednot rated
12 AWG9.1 ft4.5 ftnot rated
10 AWG14.5 ft7.3 ft4.8 ft
8 AWG23.1 ft11.6 ft7.7 ft
6 AWG36.7 ft18.3 ft12.2 ft
4 AWG58.4 ft29.2 ft19.5 ft
2 AWG92.8 ft46.4 ft30.9 ft
1/0 AWG147.5 ft73.8 ft49.2 ft
4/0 AWG296.1 ft148.0 ft98.7 ft

For a gauge's ampacity, diameter or mm², see the wire gauge chart.

Solar, Battery, Marine and Automotive: the Standard Behind Each Mode

Battery, inverter and RV circuits follow NEC 2023 (NFPA 70-2023): Table 310.16 ampacity at the 75°C termination column, with the 90°C column corrected for ambient and bundling under 310.15. Continuous loads are multiplied by 1.25, the fuse or breaker is the next rating in Table 240.6(A), and the 240.4(D) caps hold 18, 16, 14, 12 and 10 AWG to 7, 10, 15, 20 and 30 A.

Solar mode applies Article 690: under NEC 690.8(A)(1)(a)(1) the maximum circuit current is the sum of the parallel short-circuit currents times 125 percent; 690.8(B)(1) requires a conductor ampacity of at least 125 percent of that maximum before adjustment or correction, and 690.8(B)(2) checks the corrected ampacity against the maximum current. The overcurrent device is rated not less than 125 percent of the maximum current under NEC 690.9(B)(1) and must be listed for PV systems. Drop uses the operating current (Imp times strings).

Marine mode follows ABYC E-11: Table 6A ampacity by insulation rating and engine-space column, a 0.7 factor for bundles, a 16 AWG minimum, copper only, and 3 percent for critical circuits (panel feeds, electronics, pumps) or 10 percent for general lighting. Automotive mode has no open ampacity table, so it reads the Table 6A column matching the SAE J1128 insulation class, 80°C for GPT and 125°C for GXL, SXL and TXL, as a disclosed proxy. IEC 60364-5-52 installations should confirm the mm² size against their own tables.

Common DC Wire Sizing Mistakes

  • Sizing from ampacity alone. A 12 V chart that only asks for amps is a 120 V chart in disguise; length decides most low-voltage runs.
  • Running a 2,000 W inverter at 12 V. About 185 A, needing 250 kcmil copper as a continuous load under NEC 310.16; at 24 or 48 V it needs 1 AWG or 6 AWG.
  • Fusing for the load instead of the conductor. The fuse protects the wire, so it is limited to the conductor ampacity, the next standard size under NEC 240.4(B), or 150 percent under ABYC.
  • Using the 120 V tool for a battery circuit. For AC branch circuits and feeders use the wire size calculator; the battery size calculator sets the Ah of the bank feeding these cables.

Disclaimer: This calculator applies the 2023 NEC and ABYC E-11 tables to the values you enter. Adopted editions and local amendments vary; the authority having jurisdiction (AHJ) or a marine surveyor has the final say. Confirm the installation with a licensed electrician or professional engineer (PE) before energizing.

Frequently Asked Questions

What gauge wire do I need for a 2000 watt inverter at 12 volts?

About 250 kcmil copper under NEC 310.16 if the load is treated as continuous, which is the conservative reading. 2,000 W at 12 V through a 90 percent efficient inverter draws 185 A; times 1.25 that is 231 A, and the first 75°C copper size above 231 A is 250 kcmil (4/0 stops at 230 A). At 24 V the same inverter draws 93 A and needs 1 AWG; at 48 V it draws 46 A and needs 6 AWG. Inverter makers often quote 2/0 or 4/0 welding-style cable based on 105°C fine-strand ratings, which this calculator does not assume. Keep the run short and fuse it at the battery.

How far can you run 12 gauge wire on 12 volts?

At 10 A and a 3 percent drop, 12 AWG copper reaches about 9 ft one way (18 ft of wire). Relax the limit to 10 percent for lighting or accessories and the same wire reaches about 30 ft. Halve the current to 5 A and both distances double. The math is the drop formula turned around: allowed volts times 1000, divided by two times the current times 1.98 ohms per 1000 ft, the Table 8 resistance of 12 AWG at 75°C. Ampacity is not the issue here; 12 AWG carries 25 A at a 75°C termination, capped at a 20 A fuse by NEC 240.4(D).

Can I use aluminum wire for DC or solar circuits?

Yes on the NEC side, no on boats or vehicles. Battery, inverter, RV and PV circuits may use aluminum sized from the aluminum columns of NEC Table 310.16 and Table 8, which this calculator does when you select it, typically two sizes larger than copper and terminated only on lugs listed for aluminum with an oxide inhibitor. ABYC E-11 requires stranded copper for marine wiring, and automotive cable under SAE J1128 is copper, so the calculator locks those two modes to copper.

What size fuse goes with the wire?

The fuse protects the wire, not the appliance, so its rating must not exceed the conductor ampacity. Start with the design current (the load, times 1.25 if it is continuous, or 1.25 times 1.25 times Isc on a PV string), round up to the next standard rating in NEC Table 240.6(A), then check it against the conductor. NEC 240.4(B) permits the next standard size above the ampacity, ABYC allows up to 150 percent, and the 240.4(D) caps hold small conductors to 7 to 30 A. On boats and vehicles mount the fuse within 7 in of the battery or distribution point.