Power Factor Calculator

This power factor calculator finds the power factor from volts, amps and watts, any two of kW, kVA and kVAR, or the phase angle, on single-phase or three-phase loads. It also gives the angle and the apparent and reactive power, tagged lagging or leading from the load type you select. Set a target, or start from a known power factor, and it sizes the correction in kVAR and microfarads at your voltage and frequency.

By Saad Tahir, Electrical Engineer Updated

Calculator

Find the Power Factor

Common scenarios
L-L: line-to-line volts (480 V). L-N: line-to-neutral volts (277 V).
Three-phase: total of all phases.
Three-phase: line-to-neutral volts vs line current.
Volts, amps and watts can't show this, so pick it. Motors and transformers lag.

Power Factor Result

—

Enter what you know to get the power factor

Correct to a target power factor
Most installs stop at 0.95 to 0.98. A fixed bank sized for 1.00 can go leading at light load.

How this was worked out

How to Calculate Power Factor (PF = kW / kVA)

  1. Pick what you know: meter volts, amps and watts; two of kW, kVA and kVAR; or a phase angle or known power factor plus one of them.
  2. Set the phase (for three-phase, enter the voltage line to line, 480 V, or line to neutral, 277 V) and pick lagging for motors or leading for an over-corrected bank; watt readings can't show which.
  3. Read the power factor, then open Correct to a target power factor (0.95 is pre-filled); the system voltage adds microfarads and line current.

The Power Factor Formula and What the Result Means

Power factor (PF = P / S) is the share of the volt-amperes that does real work. A 240 V shop motor drawing 20 A takes 4,800 VA, yet a wattmeter reads 3,840 W, so its power factor is 3,840 / 4,800 = 0.80. Only 16 A of the 20 A is in phase with the voltage. A 12 A reactive component flows at right angles to it, trading magnetic energy with the line, and the two combine as √(16² + 12²) = 20 A. That reactive current does no work, yet still heats the conductors.

Power factor formula PF = P ÷ S
  • PF = power factor, from 0 to 1
  • P = real power in kW
  • S = apparent power in kVA: V × I ÷ 1000 single-phase, √3 × VLL × I ÷ 1000 three-phase (√3 ≈ 1.732)

Example: a bill showing 10 kW and 12.5 kVA gives 10 ÷ 12.5 = 0.800.

For a sinusoidal load the ratio equals the cosine of the angle between the voltage and current waves, so 0.80 means a 36.87° shift. Reactive power is the third side of the power triangle, Q = √(S² − P²); for the shop motor, √(4.8² − 3.84²) = 2.88 kVAR. With the power factor known, the kVA to kW calculator turns a kVA rating into usable kW.

Power factor from the phase angle PF = cos φ
  • φ = angle between the voltage and current waves, 0° to 90°
  • Q = P × tan φ, the reactive power in kVAR

Example: a 25.84° lag reads as cos 25.84° = 0.900.

Lagging current peaks after the voltage, the mark of a magnetizing winding in a motor, transformer or magnetic ballast, and a U.S. DOE motor fact sheet notes that power factor degrades below about half load. Leading current peaks first, as on a long, lightly loaded cable or an over-corrected plant. Heaters sit at 1.0.

Using the Power Factor Calculator to Size a Correction Capacitor

Parallel capacitors cancel inductive kVAR while real power stays put, so the kVAR to add is kW times the drop in tan φ.

Capacitor kVAR for a target power factor Qc = P × (tan φ1 − tan φ2)
  • Qc = capacitor reactive power in kVAR
  • P = real power in kW
  • φ1 = arccos of the present power factor; φ2 = arccos of the target

Example: 100 kW at 0.75 corrected to 0.95: 100 × (0.882 − 0.329) = 55.3 kVAR.

Capacitor kVAR per kW by Power Factor

Present PFCurrent vs unitykVAR per kW to 0.95kVAR per kW to 1.00
0.60+67%1.0051.333
0.65+54%0.8401.169
0.70+43%0.6921.020
0.75+33%0.5530.882
0.80+25%0.4210.750
0.85+18%0.2910.620
0.90+11%0.1560.484

Wye capacitors see VLL / √3, so they need three times the microfarads per phase of a delta bank.

Capacitance from kVAR C = Qc ÷ (2πf × V²)
  • C = capacitance in farads (× 106 gives µF)
  • Qc = reactive power in VAR (kVAR × 1000, a third of it per phase of a three-phase bank)
  • f = frequency in Hz; V = voltage across the capacitor

Example: 55.3 kVAR at 480 V three-phase, delta, 60 Hz: 18,433 VAR ÷ (2π × 60 × 480²) = 212 µF per phase (wye 637 µF).

The kVAR to amps calculator gives the finished bank's current, and the kW to kVA calculator shows the transformer capacity the correction frees up.

NEC Article 460 and IEC Rules for Correction Capacitors

Capacitor installations fall under NEC 2023 (NFPA 70-2023) Article 460. At 1000 V or less (Part II), NEC 460.8(A) requires capacitor circuit conductors with an ampacity of at least 135 percent of the capacitor's rated current (tied to a motor, also at least one-third of the motor circuit conductor ampacity), and NEC 460.6(A) requires discharge to 50 V or less within 1 minute of disconnection. Above 1000 V, Part III applies, with a 5 minute limit in NEC 460.28(A). IEEE Std 1459 defines power factor as P / S, IEC 60831-1 covers low-voltage self-healing capacitors, and IEC 60038 230/400 V systems use the same math at 50 Hz.

Common Power Factor Calculation Mistakes

  • Using line-to-neutral volts in the √3 formula. √3 × V × I expects 480 V; with 277 V, use 3 × V × I.
  • Reading one phase on a three-phase load. Enter the total watts of all three phases, and take a scope angle between line-to-neutral volts and line current; line-to-line volts read 30° off.
  • Sizing microfarads at 60 Hz for a 50 Hz plant. The bank comes out about 17 percent short.
  • Adding capacitors to a leading load. That pushes it further from unity; switch capacitors out or add reactors.
  • Leaving a motor overload at its old setting. With the capacitor on its load side, NEC 460.9 bases the setting on the improved power factor.

Disclaimer: This power factor calculator applies displacement power factor relationships for sinusoidal loads. It ignores harmonic distortion, which capacitors cannot correct, and does not check resonance or size conductors and protection. Capacitors stay charged after disconnection, and the work falls under NEC Article 460 and your authority having jurisdiction (AHJ), which may enforce an earlier edition; have a licensed electrician or professional engineer confirm the design.

Frequently Asked Questions

What is the formula for power factor?

Power factor is real power divided by apparent power: PF = kW / kVA, or watts / volt-amperes. Apparent power is V × A for single-phase and √3 × V × A for three-phase with line-to-line volts. For a sinusoidal load the ratio also equals cos φ, the cosine of the angle between the voltage and current waves. A load drawing 10 kW at 12.5 kVA has PF = 10 / 12.5 = 0.80 and an angle of 36.87°, and its reactive power is √(12.5² − 10²) = 7.5 kVAR. The answer always falls between 0 and 1, so a kW reading above the kVA means one of the numbers is wrong.

How do you calculate power factor for 3 phase?

Divide the total watts by √3 × line-to-line volts × line amps: PF = W / (√3 × V × I). A 480 V three-phase feeder carrying 50 A has an apparent power of 1.732 × 480 × 50 = 41,568 VA, so a total meter reading of 33,260 W gives 33,260 / 41,568 = 0.80. With line-to-neutral volts, use 3 × V × I instead (3 × 277 × 50 = 41,550 VA, the same within rounding). A 400 V, 50 Hz system carrying 60 A works the same way: 1.732 × 400 × 60 = 41,568 VA. The formula assumes balanced phases, so on an unbalanced load measure total watts and volt-amperes with a power analyzer.

How do you calculate capacitor kVAR for power factor correction?

Multiply the load kW by the difference between the tangents of the present and target angles: kVAR = kW × (tan φ₁ − tan φ₂), where each angle is the arccos of its power factor. A 100 kW load at 0.75 corrected to 0.95 needs 100 × (0.882 − 0.329) = 55.3 kVAR. As a shortcut, going from 0.80 to 0.95 takes 0.421 kVAR per kW, and from 0.70 to 0.95 takes 0.692. The capacitance then follows from C = kVAR × 1000 / (2π × f × V²), using a third of the kVAR per phase on a three-phase bank: 212 µF per phase for that load on a 480 V, 60 Hz delta bank.

How do you measure power factor?

Measure true watts with a wattmeter or power analyzer, then divide by the volt-amperes from voltage and current readings taken at the same moment: PF = W / (V × A) on single-phase, or W / (√3 × V × A) on three-phase with line-to-line volts. A 120 V circuit drawing 10 A at 1,080 W has PF = 1,080 / 1,200 = 0.90. Many clamp-on power meters display power factor directly, but a basic multimeter can't, because volts times amps alone gives volt-amperes, not watts. Take the readings at the normal working load, since a motor's power factor drops when it runs lightly loaded.