Breaker Size Calculator

Enter the load and its type to get the standard circuit breaker rating from NEC Table 240.6(A), with the 125% continuous rule, the motor, air conditioner, water heater and EV charger rules, and the minimum conductor the breaker protects. Switch to IEC 60898-1 for MCB ratings.

By Saad Tahir, Electrical Engineer Updated

Calculator

Breaker Sizing

Common circuits
Used only when the nameplate has no MOP: the rating is then 175% of RLA per NEC 440.22(A).
Adjust for your install (optional)

Breaker Rating

—

Enter a load to size the breaker

How the Breaker Size Calculator Picks a Rating

A breaker is sized from the load current and the rule that governs that load, then rounded up to a standard rating in NEC Table 240.6(A). For ordinary circuits that is the 125% rule: a non-continuous load counts at 100%, a continuous load (3 hours or more) at 125%, so 16 A continuous needs 16 × 1.25 = 20 A.

  1. Pick the standard. NEC (Table 240.6(A) ratings, 125% rule) or IEC 60898-1 MCB ratings (no 125% factor).
  2. Pick the load type. Each type routes to its own NEC article.
  3. Enter the load. Amps, or watts or kilowatts with voltage, phase and power factor. Motors take horsepower and rated voltage; air conditioners take the nameplate MCA and MOP.
  4. Calculate. You get the rating, the clause that set it, the 80% continuous limit and the smallest 75°C conductor that breaker may protect.

What size breaker do I need: the 125% rule

The device must be rated for the non-continuous load plus 125% of the continuous load (NEC 210.20(A), or 215.3 for feeders), rounded up to the next standard rating. The 80% rule is the same rule read backward: a 20 A breaker carries 16 A continuously.

Breaker rating (NEC)R ≥ k × I
  • R = next standard rating in Table 240.6(A) (amps)
  • k = 1.25 for a continuous load, 1 for a non-continuous load
  • I = load current (amps)

Example: a 48 A EV charger is continuous, so R = 1.25 × 48 = 60 A, a standard rating.

If you only know the wattage, convert it first: I = P / (V × PF), with √3 × V for three-phase. A 4,500 W water heater at 240 V draws 18.75 A; at 125% that is 23.4 A, so the breaker is 25 A. The watts to amps calculator does the conversion.

Standard breaker sizes (NEC Table 240.6(A))

The standard ratings for fuses and inverse-time circuit breakers in NEC 2023 (NFPA 70-2023), with the circuits each size usually protects.

RatingTypical use
10 ASmall dedicated loads
15 ALighting and receptacles, 14 AWG copper
20 AKitchen and garage receptacles, 12 AWG
25 A4,500 W water heater
30 ADryer, 5,500 W water heater, 10 AWG
35 A, 45 AAir conditioners and heat pumps by MOP
40 A32 A EV charger, range minimum
50 ARange, hot tub, 40 A EV charger
60 A48 A EV charger, small sub-panel
70 A5 hp 230 V motor, inverse-time breaker
80 A, 90 A, 110 ATankless water heaters, feeders
100 A, 125 A, 150 A, 175 ASub-panels, services, feeders
200 ACommon residential service
225 to 800 A225, 250, 300, 350, 400, 450, 500, 600, 700, 800 A: large services
1000 to 6000 A1000, 1200, 1600, 2000, 2500, 3000, 4000, 5000, 6000 A: switchboards

Fuses add 1, 3, 6 and 601 A.

Breaker size by load type: motors, AC, water heaters, EV chargers

Motors are the big exception. Table 430.52(C)(1) sizes the device as a percentage of the full-load current in Table 430.248 or 430.250: 250% for an inverse-time breaker, 175% for a dual-element fuse, 300% for a nontime-delay fuse. A 5 hp 230 V single-phase motor has a table current of 28 A, so its breaker may be as large as 70 A. That is a ceiling, not a target; 430.52(C)(1)(a) permits the next standard size when the percentage falls between ratings. Conductors are sized separately (NEC 430.22).

Air conditioners and heat pumps are sized from the nameplate: MCA sets the conductor and MOP caps the breaker. Without a marked MOP, NEC 440.22(A) allows 175% of the compressor rated-load current, rounded up, with a 15 A floor.

Storage water heaters of 120 gallons or less are sized at 125% (NEC 422.13). EV chargers are always continuous (NEC 625.42), so 625.41 puts a 32 A charger on 40 A and a 48 A charger on 60 A. Dryers count at 5,000 W or the nameplate, whichever is larger (NEC 220.54), hence the standard 30 A circuit. Ranges rated 8¾ kW or more get at least 40 A (NEC 210.19(C)); a 12 kW range calculates to 8 kW demand under Table 220.55 but usually lands on 50 A. NEC 422.11(E) caps any single appliance at its nameplate marking, or at 150% of its rated current when unmarked.

Next size up and the small-conductor limits (NEC 240.4)

When a conductor’s ampacity falls between standard ratings, NEC 240.4(B) permits the next higher rating up to 800 A. 240.4(D) caps 14, 12 and 10 AWG copper at 15, 20 and 30 A, which is why a 25 A water heater gets 10 AWG. Motor and air-conditioner conductors are the exception: 240.4(G) sends them to Articles 430 and 440, so their breaker may exceed the wire’s ampacity. The conductor shown here is the 75°C minimum; the wire size calculator sizes the run for length, heat and bundling, and the wire gauge chart lists each gauge.

NEC and IEC 60898-1 breaker ratings

The US rules come from NEC Articles 210, 220, 240, 422, 430, 440 and 625. Outside North America, miniature circuit breakers follow IEC 60898-1 and are coordinated with the cable by Ib ≤ In ≤ Iz under IEC 60364-4-43 and BS 7671, with no 125% uplift. The MCB ratings are 6, 10, 13, 16, 20, 25, 32, 40, 50, 63, 80, 100 and 125 A.

Common breaker sizing mistakes

  • Applying 125% to a motor. Table 430.52(C)(1) allows 250% for an inverse-time breaker.
  • Rounding down. 1.25 × 18.75 = 23.4 A is a 25 A breaker, never 20 A.
  • Putting a 30 A breaker on 12 AWG copper (240.4(D) forbids it).

Disclaimer: This breaker size calculator applies NEC and IEC 60898-1 rules to the values you enter. Nameplate markings, manufacturer instructions, local amendments and the AHJ govern. Confirm the result with a licensed electrician or professional engineer before you build the circuit.

Frequently Asked Questions

What size breaker do I need for a 240 V water heater?

A 4,500 W water heater at 240 V needs a 25 A breaker on 10 AWG copper. It draws 18.75 A, and NEC 422.13 sizes the breaker and conductors at 125% of that, 23.4 A, which rounds up to the 25 A standard rating. A 5,500 W element draws 22.9 A, so its breaker is 30 A on 10 AWG. Check the nameplate first: if the manufacturer marks a maximum breaker, NEC 422.11(E) says you cannot go above it.

What size breaker does an electric dryer need?

A household electric dryer goes on a 30 A, 240 V circuit with 10 AWG copper and a NEMA 14-30 receptacle. NEC 220.54 counts the dryer at 5,000 W or its nameplate rating, whichever is larger, so a 5,400 W dryer draws 22.5 A and needs at least 25 A; the 30 A circuit is the convention and nearly every dryer nameplate marks 30 A. A larger breaker is not allowed, because 10 AWG copper is capped at 30 A by NEC 240.4(D).

Can a breaker be larger than the ampacity of the wire it protects?

Only in two cases. NEC 240.4(B) lets you round up to the next standard rating in Table 240.6(A) when the conductor ampacity does not match a standard size, the circuit is not a multi-outlet branch circuit for cord-and-plug loads, and the next size is 800 A or less. NEC 240.4(G) lets motor and air-conditioner breakers exceed the conductor ampacity because the device is sized for starting current under Article 430 or 440 while the overload protection guards the wire. Small conductors are the hard cap: 240.4(D) limits 14 AWG copper to 15 A, 12 AWG to 20 A and 10 AWG to 30 A, and the wire gauge chart lists the 240.4(D) limit for each gauge.

What size breaker for a 5 hp motor?

A 5 hp, 230 V single-phase motor has a Table 430.248 full-load current of 28 A. Table 430.52(C)(1) allows an inverse-time breaker up to 250% of that, 70 A, or a dual-element time-delay fuse up to 175%, which is 49 A and rounds up to 50 A. Those are maximums that let the motor start; a 50 A or 60 A breaker often works. The conductors are sized separately at 125% of 28 A, or 35 A, which is 10 AWG copper at 75°C.