Fuse Size Calculator
Find the fuse rating from the load and what the fuse protects: a general AC or DC circuit, a motor, a transformer, a solar PV string, an inverter battery cable or a car audio amplifier. Each result rounds to a standard fuse size under the NEC rule for that load, names the clause, and can check the fuse against the wire it protects.
How the Fuse Size Calculator Picks a Fuse Rating
The right fuse is the smallest standard rating that covers 100% of the non-continuous current plus 125% of anything that runs 3 hours or more. A 24 A continuous load works out to 24 × 1.25 = 30 A, so it takes a 30 A fuse. Motors, transformers, PV strings and inverters each have their own NEC rule, which this fuse size calculator applies when you pick the load.
- Pick what the fuse protects, which sets the NEC rule.
- Enter the load: amps or watts, horsepower, kVA, module Isc and strings, or inverter and amplifier watts.
- Check the wire (optional) against the fuse.
- Read the rating, its clause, the voltage or DC rating it needs and the working.
What size fuse do I need: the 125% rule and the next standard size
NEC 210.20(A) sets the floor: the fuse rating can’t be less than the non-continuous current plus 1.25 times the continuous current, and you round up from there.
- F = fuse rating in amps, the next standard size in NEC Table 240.6(A)
- k = 1.25 if the load runs 3 hours or more, otherwise 1
- I = current the load draws, in amps
Example: a 1,500 W space heater on 120 V draws 12.5 A. Run continuously, it sizes at 12.5 × 1.25 = 15.6 A, so the fuse is 20 A.
From watts, I = P / (V × PF); the watts to amps calculator does that step. Standard sizes run 10 A to 6000 A, and fuses add 1, 3, 6 and 601 A. Vehicle blade fuses run 1 to 40 A at 32 V DC, so a 60 W, 12 V LED light bar (5 A, sized at 6.25 A as a continuous load) takes a 7.5 A blade.
Fuse sizing rules by load (NEC)
| Load | Fuse rule | NEC clause | Example |
|---|---|---|---|
| General circuit | 125% of continuous load, next size up | 210.20(A), 240.6(A) | 24 A continuous: 30 A |
| Motor, dual-element fuse | 175% of table FLC, next size up; 225% ceiling to start | Table 430.52(C)(1) | 5 hp, 230 V single-phase: 50 A |
| Motor, nontime-delay fuse | 300% of table FLC; 400% ceiling to start | Table 430.52(C)(1) | 5 hp, 230 V single-phase: 90 A |
| Transformer, primary only | 125% at 9 A or more; 167% below 9 A; 300% below 2 A | Table 450.3(B) | 45 kVA, 480 V, three-phase: 70 A |
| Solar PV string | 1.25 × 1.25 × Isc, at or below the module maximum | 690.8(A)(1), 690.9(B) | Isc 11.2 A: 20 A |
| Inverter battery cable | 125% of input current at the lowest input voltage | 706.30(A)(3), 706.31(B) | 2,000 W, 12 V: 300 A |
Fuse size for motors, transformers, solar strings and inverters
Motor fuses are a percentage of the table full-load current (Table 430.248 or 430.250, not the nameplate, per NEC 430.6(A)(1)). A 5 hp, 230 V single-phase motor is listed at 28 A, so its dual-element fuse may be 28 × 1.75 = 49 A, rounded up to 50 A under 430.52(C)(1)(a). If that won’t hold the start, 430.52(C)(1)(b) allows 225%: 63 A, which rounds down to 60 A because it’s a ceiling. Overload protection is sized separately (NEC 430.32).
Transformer fuses for units of 1000 V or less follow Table 450.3(B). Only its 125% cells may round up (Note 1); the 167% and 300% cells are ceilings that round down. The kVA to amps calculator gives the primary current for any rating. Secondary conductor protection (NEC 240.4(F), 240.21(C)) is outside this tool.
PV string fuses take 125% of Isc (690.8(A)(1)) and another 125% (690.9(B)(1)). They aren’t needed when the back-feed from the other strings, (N − 1) × 1.25 × Isc, stays within the module’s maximum series fuse, the industry reading of 690.9(A)(1). With 11.2 A modules rated for a 20 A fuse, two strings (14 A) need none and three (28 A) do.
Inverter fuses use the input current at rated power and lowest input voltage (706.30(A)(3), 710.12), times 1.25 (706.31(B)). A 2,000 W, 90% inverter with a 10.5 V cutoff draws 2,000 / (10.5 × 0.9) = 211.6 A, so 264.6 A and a 300 A DC-listed fuse. At 12 V nominal it would come out 250 A, a size short.
The fuse protects the wire (NEC 240.4)
If the wire’s ampacity lands between two standard fuse ratings, NEC 240.4(B) lets you take the higher one, up to 800 A. Small copper has hard caps under 240.4(D): 15 A on 14 AWG, 20 A on 12 AWG, 30 A on 10 AWG. 18 AWG (7 A) and 16 AWG (10 A) qualify only behind Class CC, CF, J or T fuses or fuses listed for that wire. Motor circuits are the exception: 240.4(G) lets a motor fuse exceed the wire’s ampacity. The wire check uses NEC Table 310.16 building-wire ratings; vehicle and marine cable differs, so size battery cable with the DC wire size calculator.
Fuse types and standards: NEC, UL 248 and IEC 60269
NEC 2023 (NFPA 70-2023) sets the ratings and UL 248 defines the fuse classes. Manufacturer catalogs list Class CC fuses up to 30 A, Class J up to 600 A and Class L from 601 A. Each fuse also needs a voltage rating at or above the circuit voltage, an interrupting rating at or above the available fault current (NEC 110.9) and, on battery and PV circuits, a DC listing (706.31(C), 690.9(B)). IEC 60269 gG fuses are chosen by Ib ≤ In ≤ Iz (IEC 60364-4-43) with no 125% uplift.
Common fuse sizing mistakes
- Sizing an inverter fuse at 12 V nominal rather than the lowest input voltage.
- Fitting a fuse bigger than the wire allows, such as 30 A on 12 AWG copper.
- Using an AC-only fuse on a battery or PV circuit.
Disclaimer: This fuse size calculator applies NEC rules to your inputs. Nameplates, manufacturer instructions, local amendments and the AHJ govern; confirm the result with a licensed electrician or professional engineer before installing.
Frequently Asked Questions
What are the standard fuse sizes?
The standard fuse sizes in NEC Table 240.6(A) are 10, 15, 20, 25, 30, 35, 40, 45, 50, 60, 70, 80, 90, 100, 110, 125, 150, 175, 200, 225, 250, 300, 350, 400, 450, 500, 600, 700, 800, 1000, 1200, 1600, 2000, 2500, 3000, 4000, 5000 and 6000 A. Fuses alone also get 1, 3, 6 and 601 A, and NEC 240.6(A) permits nonstandard ratings. Automotive blade fuses follow their own ladder of 1, 2, 3, 4, 5, 7.5, 10, 15, 20, 25, 30 and 40 A at 32 V DC. Package sizes such as glass tube, midget cartridge and blade are a separate choice from the amp rating.
How do you size a fuse?
Size a fuse from the load current: count the non-continuous load at 100% and the continuous load (3 hours or more) at 125%, then round up to the next standard rating in NEC Table 240.6(A). Then check two limits. The fuse can’t exceed what the wire may be protected at under NEC 240.4, and its voltage rating must be at least the circuit voltage, with a DC listing on battery and solar circuits. Motors, transformers, PV strings and inverters follow their own rules, which the calculator applies by mode.
What size fuse for a 1000 watt amp?
A 1,000 W RMS Class D amplifier needs about a 100 A main fuse. At roughly 80% efficiency on a 13.8 V running system it draws 1,000 / (0.8 × 13.8) = 90.6 A, and the next standard size is 100 A. A Class AB amplifier at about 60% efficiency draws 120.8 A, so it takes 125 A. The fuse protects the power wire, so that wire must be rated for it, and the fuse goes close to the battery. Check the amplifier manual too, since many list a recommended fuse.
How do you calculate fuse size for a transformer?
Calculate the rated primary current, then apply NEC Table 450.3(B). Primary current is kVA × 1000 / V on single-phase, or kVA × 1000 / (√3 × V) on three-phase. With primary-only protection the fuse is 125% of that current at 9 A or more, rounded up to the next standard size; below 9 A it’s 167% and below 2 A it’s 300%, and those two round down. A 45 kVA, 480 V three-phase transformer draws 54.1 A, so 1.25 × 54.1 = 67.7 A and a 70 A primary fuse. Units over 1000 V follow Table 450.3(A).