kW to VA Calculator: Apparent Power From a kW Load

This kW to VA calculator converts real power in kilowatts to apparent power in volt-amperes using the power factor: VA = kW × 1,000 ÷ power factor. Enter the kW and the power factor to find the VA a UPS, small generator, or transformer must supply for a kW load. The conversion is the same for single-phase and three-phase, because the power factor is all it needs. The VA always comes out higher than the kW whenever the power factor is below 1. A 1 kW load needs 1,250 VA at a 0.8 power factor.

By Saad Tahir, Electrical Engineer Updated

Calculator

Input

kW

Result

Apparent Power (VA)

How to Convert kW to VA

To convert kW to VA, multiply the real power in kilowatts by 1,000, then divide by the power factor. Apparent power in volt-amperes equals kW times 1,000 divided by the power factor, so VA = kW × 1,000 ÷ PF. The 1,000 turns kilowatts into watts, and dividing by the power factor turns real power into apparent power.

kW is the real power a load uses; VA is the total, or apparent, power a source must supply to run it. Because the power factor is 1 or less, the VA always comes out equal to or higher than the kW in watts. Most generators and motors run near a 0.8 power factor, so the VA a source must supply runs well above the load's kW. To reverse this, the VA to kW calculator multiplies by the power factor and divides by 1,000.

kW to VA Formula

kW to VA Formula VA = kW × 1000 ÷ PF
  • VA = apparent power in volt-amperes
  • kW = real power in kilowatts
  • PF = power factor, 0 to 1 (the ratio of real to apparent power)

Example: a 1 kW load at 0.8 power factor needs 1 × 1000 ÷ 0.8 = 1,250 VA.

There is no voltage, phase, or three-phase factor in this conversion. The power factor and the 1,000 are all you need, so a three-phase kW load converts to VA the same way a single-phase one does. A power factor of 1, a purely resistive load, makes the VA equal to the kW in watts; any lower power factor makes the VA larger.

How to Use the kW to VA Calculator

  1. Enter the real power in kW. This is the working load, or the kW rating of a device or generator.
  2. Enter the power factor. Use the load's actual value if you know it, 0.8 for a typical generator or motor load, or 1 for a purely resistive load like a heater.
  3. Read the apparent power in VA. That is the volt-amp rating a UPS, generator, or transformer needs to supply the load.

The power-factor default is 0.8, the generator-set convention. For resistive loads such as heaters, use 1.0, where the VA equals the kW expressed in watts.

kW to VA formula diagram showing VA equals kW times 1000 divided by power factor, with 1 kW needing 1250 VA, 1111 VA, and 1000 VA at power factors 0.8, 0.9, and 1.0
Apparent power in VA equals kW times 1,000 divided by the power factor, so the same 1 kW needs more VA as the power factor falls.

kW to VA Worked Examples

Example 1: 1 kW at 0.8 Power Factor

At a 0.8 power factor:

VA = 1 × 1,000 ÷ 0.8 = 1,250 VA

Since 1,000 VA is 1 kVA, that result is also 1.25 kVA.

Example 2: 5 kW at 0.8 Power Factor

A 5 kW load at a 0.8 power factor needs:

VA = 5 × 1,000 ÷ 0.8 = 6,250 VA

So a 5 kW load calls for a source rated at least 6,250 VA, which is 6.25 kVA. A UPS or generator has to cover the apparent power, not just the real power.

Example 3: 3 kW at 0.9 Power Factor

A 3 kW load with a better 0.9 power factor needs:

VA = 3 × 1,000 ÷ 0.9 = 3,333 VA

The higher the power factor, the closer the VA is to the kW in watts, because less of the current is reactive.

Example 4: 2 kW Resistive Load (Power Factor 1.0)

A purely resistive load, such as a 2 kW heater, runs at a power factor of 1:

VA = 2 × 1,000 ÷ 1.0 = 2,000 VA

Here the VA equals the kW expressed in watts, because all the apparent power does real work.

kW to VA Conversion Chart

This chart gives the apparent power in VA for common kW loads at three power factors. The VA falls as the power factor rises, and equals the kW in watts only at a power factor of 1. Above a few kW, the apparent power is usually written in kilovolt-amperes; the kW to kVA calculator gives the same figure in kVA.

Real PowerVA at PF 0.8VA at PF 0.9VA at PF 1.0
0.5 kW625 VA556 VA500 VA
1 kW1,250 VA1,111 VA1,000 VA
2 kW2,500 VA2,222 VA2,000 VA
3 kW3,750 VA3,333 VA3,000 VA
5 kW6,250 VA5,556 VA5,000 VA
7.5 kW9,375 VA8,333 VA7,500 VA
10 kW12,500 VA11,111 VA10,000 VA
15 kW18,750 VA16,667 VA15,000 VA
20 kW25,000 VA22,222 VA20,000 VA
50 kW62,500 VA55,556 VA50,000 VA
100 kW125,000 VA111,111 VA100,000 VA

How Many VA Is 1 kW?

One kW works out to 1,250 VA at the usual 0.8 power factor. That figure eases toward 1,000 VA as the load becomes more resistive and the power factor climbs to 1. Since 1,000 VA is 1 kVA, the same 1 kW is 1.25 kVA at 0.8, so the volt-ampere is just the smaller unit for the identical apparent power.

Sizing diagram showing a 1 kW load multiplied by 1000 and divided by a 0.8 power factor giving 1250 VA, rounded up to the next standard VA rating
A 1 kW load needs 1,250 VA at a 0.8 power factor; round up to the next standard VA rating.

This is why a load's kW figure and the VA rating of the equipment that feeds it are not the same number. The kW is the real power the load consumes; the VA is the total power the UPS, generator, or transformer must be built to supply. The lower the power factor, the further apart the two numbers sit.

kW to VA for Sizing a UPS or Transformer

kW to VA is the conversion behind sizing small equipment from a known real-power load. When you know a load in kW and need the VA rating of the UPS, generator, or control transformer that will carry it, multiply by 1,000 and divide by the power factor. A 2 kW load at a 0.8 power factor needs 2,500 VA, so a 2,500 VA source is the minimum, and the next standard size up leaves headroom.

Small equipment such as a plug-in UPS or a control transformer is rated in VA, so this is the figure to match. For larger loads measured in kW, the apparent power is easier to read in kilovolt-amperes, and the kW to kVA calculator sizes those directly. Generator sets are rated at a 0.8 power factor by convention under ISO 8528, the generator-set standard, and apparent, real, and reactive power are defined in IEEE Std 1459, the IEEE standard for electric power quantities.

Why VA Is Higher Than kW

VA is higher than the kW (in watts) whenever the power factor is below 1. The kW is real power, the part that does useful work; VA is apparent power, the total the source must supply, including the reactive current that motors and transformers draw but that does no net work. Dividing the kW by the power factor adds that reactive part back in. For the full comparison of real and apparent power, and when to use each, the kVA to kW calculator covers kW versus kVA, and for what a volt-ampere is, the amps to VA calculator defines the unit.

Why kW to VA Needs Only the Power Factor

Converting kW to VA needs the power factor and nothing else. There is no voltage term, no phase, and no three-phase factor, because the current conversions were already finished when the load was expressed in kW. The √3 that appears in three-phase current formulas scales between line and phase quantities, so it has no job in this step. A 5 kW load calls for 6,250 VA at a 0.8 power factor on a single-phase or a three-phase supply alike. When a nameplate does not state the power factor, 0.8 is a safe working value for a generator or motor load and 1.0 for resistive heating.

Common Mistakes When Converting kW to VA

  • Assuming kW equals VA. They match only at a power factor of 1; at 0.8, a 10 kW load is 12,500 VA, not 10,000 VA.
  • Forgetting the 1,000. kW to VA multiplies by 1,000 as well as dividing by the power factor; leaving it out gives an answer a thousand times too small.
  • Adding a three-phase factor. VA = kW × 1,000 ÷ PF is the same for any phase; the √3 belongs to the current conversions.
  • Sizing to exactly the calculated VA. Round up to the next standard rating and leave a margin for inrush and growth.
  • Using the wrong power factor. The VA scales inversely with it, so a guessed power factor gives a guessed answer. Use the nameplate value where you can.

Disclaimer: This calculator converts real power to apparent power at the power factor you enter. Actual UPS, generator, and transformer sizing also depends on inrush, load type, harmonics, and a safety margin. Always verify against manufacturer data and your local electrical code, and consult a licensed electrician or professional engineer for equipment selection and installation. Generator ratings follow standards such as ISO 8528; confirm the assumed power factor on any nameplate.

Frequently Asked Questions

How do you convert kW to VA?

Multiply the real power in kW by 1,000, then divide by the power factor: VA = kW × 1,000 ÷ PF. The 1,000 converts kilowatts to watts, and dividing by the power factor (0 to 1) converts real power to apparent power. For example, a 1 kW load at a 0.8 power factor is 1 × 1,000 ÷ 0.8 = 1,250 VA. There is no voltage or phase in the formula.

How many VA is 1 kW?

It depends on the power factor. VA equals kW × 1,000 ÷ power factor, so 1 kW is 1,250 VA at a 0.8 power factor, 1,111 VA at 0.9, and 1,000 VA only at a power factor of 1. Since 1,000 VA is 1 kVA, that is the same as saying 1 kW is 1.25 kVA at 0.8.

What is 5 kW in VA?

At a 0.8 power factor, 5 kW is 5 × 1,000 ÷ 0.8 = 6,250 VA; at 0.9 it is 5,556 VA; and at a power factor of 1 it is 5,000 VA. So a 5 kW load needs a source rated at least 6,250 VA, or 6.25 kVA, at the usual 0.8 power factor.

Is VA equal to kW?

No. VA (volt-amperes) is apparent power, the product of volts and amps; kW is real power, the part that does useful work. The power factor links them: VA = kW × 1,000 ÷ power factor. On any load with a motor or electronics, the VA is higher than the kW in watts, and the two match only at a power factor of 1.

Does kW to VA change for three-phase?

No. VA = kW × 1,000 ÷ power factor is the same for single-phase and three-phase. There is no separate three-phase formula and no √3 here, because the three-phase factor and the voltage were already accounted for when the load was expressed in kW. A 5 kW load needs 6,250 VA at a 0.8 power factor whether it is single-phase or three-phase.

What is 1 kW in kVA?

At a 0.8 power factor, 1 kW is 1 ÷ 0.8 = 1.25 kVA; at 0.9 it is 1.11 kVA; and at a power factor of 1 it is 1 kVA. Because 1 kVA is 1,000 VA, this matches the VA figure divided by 1,000. The kW to kVA calculator gives the apparent power directly in kVA.

Need more electrical tools?

View All Calculators